Communication box instruction manual

Communication box instruction manual

Classification:
Technical Information
Author:
Source:
Release time:
2019/02/18
[Abstract]:
1. Communication protocol DCHP series products use Modbus RTU universal serial port protocol and RS485 (half duplex) network hardware interface. The specific regulations are as follows:
  1. Communication protocol
  DCHP series products use Modbus RTU universal serial port protocol and RS485 (half duplex) network hardware interface.
  The specific regulations are as follows:
 
 

name

the way

Remarks

Baud rate

9600

Bit/second

Data bit

8

Bit

Stop bit

1

Bit

check

even

 

Flow control

no

 


  The hardware address of the ESP power supply device adopts the “8421BCD” code dialing code:
 
  The DIP switch is set to 1 (8421BCD code), and the corresponding device address is set to 1;
 
  The DIP switch is set to 2 (8421BCD code), the corresponding device address is set to 2, and so on.
 
  When multiple devices communicate, the addresses cannot be the same, and the dialing settings are recommended to be continuous.
 
  If Ethernet communication is used, port number 502, dial switch is the same as above, and the device IP address is correspondingly:
 
  The DIP switch is set to 1 (8421BCD code), and the device IP address is 192.168.4.161;
 
  DIP switch set 2 (8421BCD code), device IP address 192.168.4.162;
 
  The DIP switch is set to 3 (8421BCD code), the device IP address is 192.168.4.163, and so on.
 
  When multiple devices communicate, the addresses cannot be the same, and the dialing settings are recommended to be continuous.
 
  2, function address
  All data types: read-only area 3x, readable and writable area 4x, unsigned short (2 Byte, 16-bit)。 Readable and writable area 0x, bit type (Bit, 1 bit)。
 
Table 1-1 Read-only area data address
 

3x (numeric) unsigned short (2 Byte, 16 bit):unshort

address

Features

unit

Remarks

7

 Interlocking state

 

When the safety interlock is used for emergency stop, the interlock status display: 0 means no external emergency stop signal is received, and non-zero means external emergency stop signal is received.

57

Output frequency

Hz

Operating state parameter

58

Oil temperature

Operating state parameter

59

IGBT temperature

Operating state parameter

60

Flash number

Times/minute

Operating state parameter

61

Primary current

V

Operating state parameter

62

Primary current

A

Operating state parameter

63

Secondary voltage

kV

Run the status parameter, read the address value of the main control board, and divide it by 10 to display it on the host computer (unit kV)

64

Secondary current

mA

Operating state parameter

65

Power status

 

Status data, see Table 1-2

66

Error alarm

 

Alarm data, see Table 1-3

  Unsigned short (2 Byte, 16 bit):unshort

Table 1-2 Power status data bit meaningTimes/minute
 
 

Serial number

D0~D15

Indicates information content

Remarks

1

D0

Running light indication

1: its status is valid
 
0: its status is invalid
 
(D0 is the lowest)

2

D1

Stop light indication

3

D2

Alarm light indication

4

D3

 

5

D4

 

6

D5

 

7

D6

 

8

D7

 

9

D8

 

10

D9

 

11

D10

 

12

D11

 

13

D12

 

14

D13

 

15

D14

 

16

D15

 

 
  Table 1-2 Error alarm data bit meaning

序号

D0~D15位

表示信息内容

备注

1

D0

电场闪络

1:其状态有效

0:其状态无效

D0为最低位)

2

D1

输出过压比较超限

3

D2

4

D3

IGBT报警

5

D4

输入过流超限

6

D5

输出过压软件超限

7

D6

输出开路

8

D7

输出过流

9

D8

油温超限

10

D9

IGBT温度超限

11

D10

一次电压故障

12

D11

输入三相故障

13

D12

电感温度报警

14

D13

使用期限报警

15

D14

主控板错误报警

16

D15

电场短路

  
Table 2-1 Readable and writable area data address

4x(数值型)无符号短整型(2 Byte,16位):unshort

地址

功能

单位

备注

11

电流给定

mA

设备运行目标值

12

电压给定

   kV

设备运行目标值,界面输入值(单位kV)在上位机乘以10以后,再写入主控板该地址。

13

电晕电压

kV

临界反电晕电压点

14

电晕电流

mA

临界反电晕电流(当运行电压低于电晕电压设置且运行电流大于电晕电流设置时,高频电源会自动复位重启一次用以跳出临界反电晕状态)

22

工作模式

 

赋值(调试=0,开路=1, 连续=2)选择模式;正常工作状态为“连续”模式。

25

闪络设置

次/

1分钟内若发生该次数闪络则降电压

26

客户密码设置

 

用于修改设置参数,输入正确密码后,方可被允许进行参数设置。

67

降压设置

%

用于喷淋/震打时提前降电压运行,设备接收到外部降压信号(无源常闭)后,按照“电压给定”乘以此(降压设置)百分比后的目标值运行。

无符号短整型(2 Byte,16位):unshort

写入方式规定选择“有变化时写入”,不允许“连续写入”方式。

 
  Table 2-2 Readable and writable area data address

0x(开关量)无符号短整型(2 Byte,16位)

地址

功能

单位

备注

11

启动/停止

 

开关机

12

联锁

 

测试按钮

13

降压

 

测试按钮

17

一键恢复

 

恢复出厂参数

无符号短整型(2 Byte,16位):unshort

写入方式规定选择“有变化时写入”,不允许“连续写入”方式。

 
 
  Note: When configuring the upper computer, please ensure that the addresses of the same interface are continuous to ensure the communication speed.
  The above 1 blue font indicates device operating parameter information and parameter settings;
  2 red font, indicating the customer password that needs to be input when modifying the parameters. The system allows the parameter modification after entering the correct password.
  3 purple font, indicating equipment auxiliary functions, including safety interlock, spray/shock buck, one-button recovery;
 
  3, the upper machine configuration history query
  Historical data record:
 

3x(数值型)无符号短整型(2 Byte,16位)

地址

功能

单位

7

联锁状态

 

58

油温

59

IGBT温度

63

二次电压

kV

64

二次电流

mA

无符号短整型(2 Byte,16位):unshort

  Historical alarm record:

序号

D0~D15位

表示信息内容

备注

1

D0

电场闪络

1:其状态有效

0:其状态无效

D0为最低位)

2

D1

输出过压比较超限

3

D2

4

D3

IGBT报警

5

D4

输入过流超限

6

D5

输出过压软件超限

7

D6

输出开路

8

D7

输出过流

9

D8

油温超限

10

D9

IGBT温度超限

11

D10

一次电压故障

12

D11

输入三相故障

13

D12

14

D13

15

D14

16

D15

电场短路

 
  Note:
  1. For some systems, the address offset bit is 1.
  2. The write mode specifies that “write when there is change” is selected, and the “continuous write” mode is not allowed.
  3. Hollysys system: When adding an address, you cannot “create redundant address bits” (addresses that do not exist in the above table)。 When adding the first address to add the address length beyond the address bit provided above, if you delete again, the write error address will still appear.